TROUBLESHOOTING
● Ducted (Medium Static) with EconoFresh Kit
(To Fan Motor)
< Checking for Fan Motor >
Remove the connector of the fan motor and measure the resistance value between each of the pins (twice).
Check whether the resistance value is over or not according to the Decision Basis shown below. When
performing the second measuring, make sure to change the tester (Red/ Black).
2 PG (Blue)
3 Vsp (Yellow)
4 Vcc (White)
5 GND (Black)
8 Vm (Red)
Connector for Fan Motor
3-30
LED1
CN201
1st Measurement
Resistance
Tester
Red
Black
PG
GND
Vsp
GND
Vcc
GND
Vm
GND
PCN201
(To TB1)
2nd Measurement
Tester
Value
W
Red
Black
GND
PG
GND
Vsp
GND
Vcc
GND
Vm
Decision Basis
Resistance
Resistance values of both
Value
1st and 2nd measurings
are over 10W
W