Control and status byte

Register communication
Control byte (for register communication)
The control byte (CB) is located in the output image [} 34], and is transmitted from the controller to the
terminal.
Bit
CB.7
CB.6
Name
RegAccess R/W
Key
Bit
Name
CB.7
RegAccess
CB.6
R/W
CB.5 to CB.0
Reg. no.
Status byte (for register communication)
The status byte (SB) is located in the input image [} 34], and is transmitted from terminal to the controller.
Bit
SB.7
SB.6
Name
RegAccess R/W
Key
Bit
Name
SB.7
RegAccess
SB.6
R
SB.5 to SB.0
Reg. no.
Process data mode
Control and status byte in process data mode
In process data mode the control and status bytes of the KL6224 currently have no addi-
tional function.
Note
Control byte in process data mode
The control byte (CB) is located in the output image [} 34], and is transmitted from the controller to the
terminal.
Bit
CB.7
Name
RegAccess -
Key
Bit
Name
CB.7
RegAccess
CB.6 to CB.0
-
38
CB.5
CB.4
Reg. no.
Description
1
Register communication switched on
bin
0
Read access
bin
1
Write access
bin
Register number:
Enter the number of the register [} 39] that you want to read or write
here.
SB.5
SB.4
Reg. no.
Description
1
Acknowledgement for register access
bin
0
Read access
bin
Number of the register that was read or written.
CB.6
CB.5
-
Description
0
Register communication off (process data mode)
bin
0
reserved
bin
Version: 2.0.0
CB.3
CB.2
SB.3
SB.2
CB.4
CB.3
-
-
CB.1
CB.0
SB.1
SB.0
CB.2
CB.1
-
-
CB.0
-
KL6224