13.8 Motor turbine (Fault 5018)
Display:
Description:
Cause and Remedy:
13.9 Output 230V (Fault 5019, 5022, 5023)
Display:
Description:
Cause and Remedy:
1310 Output 230V-2 (Fault 5020, 5024, 5025, 5027, 5029, 5030)
Display:
Description:
Cause and Remedy:
13.11 Hopper Empty - Motor res 1 (Fault 5021)
Display:
Description:
Cause and Remedy:
PE 607 USA_FA 2.1
[5018] PE Motor Turbine
Vaccuum turbine not running (Exit VAK)
Motor unplugged
Motor defect
Fuse F1, suction circuit
board defective
[5019] PE Ignition
[5022] PE Magnetic valve
[5023] PE Motor cleaning
No function of output ZUEND (Ignition)/MA (Magnetic valve)/ RM (Motor cleaning)
Output unplugged
Current value above the
maximal Limit
Current value under the
minimal Limit
[5020] PE Motor ashbox (Output AV)
[5024] PE Flue gas fan (Output SZ)
[5025] PE Cirkulationspump (Output UW)
[5027] PE Motor ext auger2 (Output RES2)
[5029] PE Motor boiler auger (Output ES)
[5030] PE Combustion Fan (Output LUFT)
No function of the respective motor/pump/fan
Motor/pump/fan
unplugged
Motor/pump/fan defect
[5021] PE Hopper empty / Motor RES1 (for 36-56 kW, Pellematic Condens or
PEB)
No function of PE motor res 1
Motor unplugged
Motor defect
No pellets available
Plug in motor, check cable connections
Replace motor
Replace fuse
Connect plug, check cable wiring
Check limits
Check limits
Connect plug, check cable wiring
Replace motor/pump/fan
Plug in motor, check cable connections
Replace motor
Refill storage-Room / supply tank