Malfunction report
13.3 Bus (Fault 4005, 4006, 4007, 4015, 4016)
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
13.4 Combustion chamber sensor (Fault 5010, 5011)
Display:
Description:
Cause and Remedy:
Display:
Description:
[4005] BUS HCR
Time-Out of BUS-connection from touch operating device to heating controller
Wrong cable connection
No power supply available
Fuse in heating controller
defect
[4006] BUS PE
Time-Out of BUS-connection from touch operating device to boiler controller
Wrong cable connection
No power supply available
Fuse in heating F2 defect
[4007] BUS Remote
Time-Out of BUS-connection of remote control
Wrong cable connection
Remote controll defect
[4015] BUS Remote Touch
Time-Out of BUS-Connection from remote controll to Touch operating device
Wrong cable connection
Wrong softwareversion
[4016] BUS Master
Missing BUS connection to master-operating device
Wrong cable connection
[5010] PE Combustion sensor BS
Combustion chamber sensor fracture, measuring circuit from combustion chamber
sensor is open – Input FRT
Sensor not connected
Sensor defect
Sensor cable defect
Sensor temperature too
high
[5011] PE Combustion sensor SC
Combustion chamber sensor short circuit, measuring circuit from combustion
chamber sensor short circuit – Input FRT
Check cable connection
►
Connect heating controller to BUS
►
Replace fuse
►
Check cable connection
►
Connect heating controller to power supply (X21)
►
Replace fuse F2
►
Check cable connection
►
Replace remote controll
►
Check cable connection
►
Check version of software
►
Check cable connection
►
Connect sensor at input
►
Measure sensor (approx. 5 mV at 125°C) replace if
►
required
Replace sensor
►
Sensor temperature above measuring range
►
(1100°C)