13.6 Analog input (Fault 5014, 5015, 5016, 5017)
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
13.7 Eingang AnalogIN (Fault 5046)
Display:
Description:
Cause and Remedy:
[5013] PE Underpressure box SC
Negative draft input short-circuit, measuring circuit from negative draft measure-
ment is shorted out – Input UP
Signal incorrect
Signal cable defect
Signal too high
[5041] [5042] PE Low underpressure
Negative draft pressure in boiler is not achieved [5041] or is too high [5042] – Exit
LUFT (SMART + Condens) / Output SZ (PE+PEK)
Negative draft tube
disconnected
Negative draft does not
change
Negative draft pressure
too low
Negative draft pressure
too high
[5014] / [5016] PE Analog input 1/2 BS
Analog input 1/ 2 sensor fracture, measuring circuit of Analog input sensor open –
Output AE1 / AE2
Signal incorrect
Signal cable defect
Level detection system ac-
tivated (valid for AE2)
[5015] / [5017] PE Analog input 1 /2 SC
Analog input 1 / 2 sensor short circuit, measuring circuit of Analog input sensor is
shorted out – Input AE1/AE2
Signal incorrect
Signal cable defect
Signal too high
[5046] External Error SC
AnalogIN input short circuit, measuring circuit of Analog input sensor is short-
ed out – Input AnalogIN
Signal incorrect
Signal cable defect
Signal too high
Check poarity and signal (0-10V)
Replace sensor
Signal above 10V
Connect up negative draft tube
Check negative draft tube for leaks.
Check flue gas tube for blockage.
Close boiler door, check tube to negative draft
sensor, check whether boiler flue gas outlet is
clear, check whether condensation heat exchan-
ger is clear. Make sure flue gas fan is running.
Check induced draft blower
Check poarity and signal (0-10V)
Replace sensor
Check settings
Check poarity and signal (0-10V)
Replace sensor
Signal above 10V
Check poarity and signal (0-10V)
Replace sensor
Signal above 10V