ABB Zenith ZTG 30 Operation, Maintenance And Installation Manual page 88

Automatic transfer switches
Table of Contents

Advertisement

88
Automatic transfer switch, I/O contacts
Generator start/stop
1
2
3
G
NO NC
C
Output relay features
1
2
3
5
6
G
C
NO NC
C
O1
Fire Fighting applications
5
6
10
11
12
+
-
FIRE
24V
C
O1
C
Input contact features
Common input
10
11
12
13
14
-
+
FIRE
24V
C
I1
I2
Z e n i t h Z T G S e r i e s AT S , O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E
Common, voltage supply
5
6
10
11
Generator start/stop NO
Generator start/stop NC
+
FIRE
24V
O1
C
10
11
12
13
Common, voltage supply
Programmable output
-
+
(default; Product available)
FIRE
24V
C
I1
Fire fighting input 24 Vdc (+)
13
14
Fire fighting input 24 Vdc (-)
I1
I2
Programmable input
(default; Remote test on load)
Programmable input
(default; Remote test off load)
Cabling /
Terminal
24-14 AWG
12
13
-
C
I1
24-14 AWG
24-14 AWG
24-14 AWG
Rating / Remark
Stripping length; 0.255"
1 5 A@250 Vac (AC-1), 5 A@30 Vdc
2
3
5 5 A@250 Vac (AC-1), 5 A@30 Vdc
6
Only in ZTGD-types, delayed
transition, I – O – II
10
11
Do not connect to any
power supply
12
24 Vdc 5 mA
13
14
Only in OXB_-types, delayed
transition, I – O – II or II – O – I
SELV