62
Z e n i t h Z T G S e r i e s AT S , O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E
—
5.6 Using Ekip Com _ -modules
Suitable Ekip Com_ -modules are:
• Ekip Com Modbus RTU
• Ekip Com Profibus DP
• Ekip Com DeviceNet
• Ekip Com Modbus TCP
• Ekip Com Profinet
• Ekip Com EtherNet/IP
5.6.1 Ekip Com Modbus RTU -module
The Ekip Com Modbus RTU is a communi-
cation accessory module, that integrates
the automatic transfer switch in an indus-
trial remote supervision and control net-
work. The module is suitable for all ZTG(D)
30-1200 A, 200-480 Vac automatic trans-
fer switches.
It can be connected to a RS-485 network
with a Modbus RTU communication pro-
tocol, and allows you to:
• Connect the automatic transfer switch
to the network, with dialog functional-
ity.
• Provide the status information of the
automatic transfer switch (e.g. open,
closed).
For the communication lines W1 and W2,
Belden type 3105A or equivalent cables
must be used.
—
Fig. 5.11 Ekip Com Modbus RTU -module