Z e n i t h Z T G S e r i e s AT S , O P E R AT I O N , M A I N T E N A N C E , A N D I N S TA L L AT I O N G U I D E

4.3 Menus and Parameters

Operation
Bypass Time Delay
HMI Control Keys (I, II)
Energy Counters
Parameters
System parameters
Start Automatic Configuration
Power distribution systems (see Fig. 2.2)
Source 1
Source 2
Rated Voltage
200 V (3ph), 208 V (3ph), 220 V (3ph), 230 V (3ph), 240 V (3ph), 277 V (3ph), 347 V
(3ph), 380 V (3ph), 400 V (3ph)*, 415 V (3ph), 440 V (3ph), 460 V (3ph), 480 V (3ph),
200 V (1ph), 220 V (1ph), 230 V (1ph), 240 V (1ph), 254 V (1ph), 265 V (1ph), 277 V
(1ph), 318 V (1ph), 333 V (1ph), 347 V (1ph), 380 V (1ph), 400 V (1ph), 415 V (1ph),
440 V (1ph), 460 V (1ph), 480 V (1ph)
Rated Frequency
50 Hz*
60 Hz
Neutral Position
Pole 4*
Pole 1
Phase Sequence
ABC*
ACB
Not Enabled
Bypass any currently running time delay
Enabled*
Disabled
Reset
1 Phase, 2 Wire
2 Phases, 3 Wire (Split Neutral)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
1 Phase, 2 Wire
2 Phases, 3 Wire (Split Neutral)
3 Phases, no Neutral (3ph3w)
3 Phase with Neutral (3ph4w)*
3 Phase, High-Leg Delta
*Default
*Default
Continued on the next page