5.6.2.1 LED indications
The following table illustrates the possi-
ble signals, and their meaning:
LED
Power LED, green
On, with two quick flashes per second
RX LED, green
TX LED, green
Table 5.9 Indication / Ekip Com Profibus DP -module
5.6.2.2 Termination resistor
The Ekip Com Profibus DP modules pro-
vide the possibility to insert a 220 Ω ter-
mination resistor on the RS-485 bus, by
setting the DIP-switches Rterm (1 and 2)
on the side of the modules, in position
ON.
Fig. 5.15 Signals of Ekip Com Profibus DB -module
Indication
On fixed
On, with one flash per second
On, fixed
On, flashing
In the event of termination of the bus, a
390 Ω pull-up or pull-down resistor must
also be inserted on the lines, by setting
the DIP-switches Rpol (3 and 4), in posi-
tion ON.
These options must be selected before in-
stallation of the modules.
Fig. 5.16 Termination resistor; To enable the Rterm, the
dip-switches 1 and 2 must be positioned to ON. When Rterm
is activated, the Rpol must also be activated by turning
dip-switches 3 and 4 to ON-position. These options must
be selected before the installation of the modules
Off
Power supply and communication with the
Power supply and communication with
Power supply present, and communication
Off
Communication not active.
Communication active.
Off
Communication not active.
Communication active.
ON IA
1 2 3 4
Rterm Rpol
120Ω
on
off
Description
Power supply absent.
device present.
device present.
with device absent.
on
off