Setup procedure utadvanced quick setting (ph control)
Hide thumbs Also See for UT52A:

Advertisement

Quick Links

Technical
Information
TI 04L01L01-01EN
Foreword
The contents of this document are subject to change without prior notice as a result of improvements in performance or functionality.
Copying or reproduction by any means of all or any part of the contents of this document without permission is strictly prohibited.
Use of this document is at the users risk.
■ Overview
This is an example of wiring and settings using the UTAdvanced Quick Setting function for "pH Control."
For more details, see the user's manual.
■ Relevant models
Standard models of the UT52A and UT55A (if there are 2 types of pharmaceuticals, select the
heating/cooling model)
■ System
Current input signal
4–20 mA
pH meter
converter
0–14 pH
Plant A waste liquid -->
Plant B waste liquid -->
Plant C waste liquid -->
■ Wiring
Power
supply
Setup Procedure
UTAdvanced Quick Setting (pH Control)
Current input signal
4–20 mA
pH meter
sensor
UT52A, UT55A Standard Models
Current
output
4–20 mA
PV
Transmission
output
This document is subject to change without notice.
■ Nonlinear type
Chemical dosing pump
■ Sampling control
Effluent
Current input
4–20 mA
PV
Current
input
203
Current output
4–20 mA
Control gain is switched by the Gap Gain Control
function
Sampling can be controlled to interpolate dead time
pH meter
2011.12.16 1st Edition (YK)
TI 04L01L01-01EN

Advertisement

loading
Need help?

Need help?

Do you have a question about the UT52A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for YOKOGAWA UT52A

  • Page 1 This is an example of wiring and settings using the UTAdvanced Quick Setting function for "pH Control." For more details, see the user's manual. ■ Relevant models Standard models of the UT52A and UT55A (if there are 2 types of pharmaceuticals, select the heating/cooling model) ■ System ■...
  • Page 2 ■ Settings To set the sample PID control, input type (4 to 20 mA), and current control output (4 to 20 mA), set the parameters below. (1) Select the desired parameter with the UP or DOWN key (2) Press SET/ENTER (the setting value blinks) (3) Change the setting with the UP or DOWN key (4) Press SET/ENTER to set the new value (the setting value stops blinking but remains bright)
  • Page 3 Set RH (maximum value of PV input range) to 20.00 mA (the initial value). MAXIMUM MAXIMUM VALUE OF PV VALUE OF PV INPUT RANGE INPUT RANGE 20.00 20.00 MINIMUM MINIMUM Set RL (minimum value of PV input range) to 4.00 mA (the initial value). VALUE OF PV VALUE OF PV INPUT RANGE...
  • Page 4 Revision Information Document name: Setup Procedure: UTAdvanced Quick Setting (pH Control) Document number: TI 04L01L01-01EN First edition: December, 2011 Newly released TI 04L01L01-01EN 2011.12.16-00 This document is subject to change without notice.

This manual is also suitable for:

Ut55a