Data
400 V 3N a.c. / 400 V 2N a.c. / 230 V N a.c.
Supply voltage
+10/-15%, 30 VA, 50 Hz
Main switch
Automated fuse, 4 terminals, 16 A, SIL-approved
Sensor S2
Not used
Sensor S3, S3B,
Pt 1000 or
S4, S5, S5B, S6,
PTC 1000 ohm / 25°C
S6B
(All must be of the same type)
Measuring range -60 to +120°C
Controller
Accuracy
Pt 1000 sensor
I-reading
L11 - L18
Display
2 plugs for connecting external display
External display
EKA 163B or 164B
Signal from contact functions
Digital inputs
Requirements to contacts: None
DI1, DI2, DI3,
Cable length must be max. 15 m
DI4, DI5, DI6
Use auxiliary relays when the cable is longer
Digital inputs
230 V a.c.
DI7, DI8
Electrical con-
Max. 2.5 mm
nection cable
DO1-DO8
Relays
Alarm relay
Solid state
DOA (for coil)
output
Analogue
AO1
voltage outlet
0 to +55°C, During operations
-40 to +70°C, During transport
Environments
20 - 80% Rh, not condensed
No shock influence / vibrations
Enclosure
IP 20
Weight
3.8 kg
Fixed
Data
communication
Extension options
Power reserve
24 hours
for the clock
EU Low Voltage Directive and EMC demands re
CE-marking complied with
Approvals
LVD-tested acc. EN 60730-1, EN 60730-2-1 and
EN 60730-2-9
EMC-tested acc. EN 61000-6-2 and EN 61000-6-3
*) Gold plating ensures make function with small contact loads.
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
40
±1 K below -35°C
± 0,5 K between -35 to +25°C;
±1 K above +25°C
±0,3 K at 0°C
±0,005 K per degree
0-10 A: +/- 15%
min. +/- 1A
On: DI > 80 V a.c.
Off: DI < 24 V a.c.
2
Max. 16 A (12) A
I max: (adjustable 4-16 A)
I max. = 0 = cut out cancelled
4 (3) A. Min. 100 mA*
Max. 240 V half wave rectified
Max. 0.5 A
Leakage < 1 mA
Max. 1 coil
Electronic coil controller EEC may
not be used
0-10 V
R
> 1 kΩ
Load
MODBUS
LON RS485
User Guide RS8GR602 © Danfoss 2016-10
AK-CT 450A