Rail heat during defrost cycle
Here you can set how the rail heat is to be regulated during a defrost cycle.
0: No rail heat
1: No change; continues as during regulation.
2: 100% on
If you wish to see the temperature at the defrost sensor, push the controller's
lowermost button. (May be changed to another function in o92.)
If you wish to start an extra defrost, push the controller's lowermost button for
four seconds.
You can stop an ongoing defrost in the same way
Fan
Fan stop temperature
The function stops the fans in an error situation, so that they will not provide power
to the appliance. If the defrost sensor S5 registers a higher temperature than the one
set here, the fans will be stopped. There will be re-start at 2 K below the setting.
The function is not active during a defrost or start-up after a defrost.
With setting +50°C (=max. value) the function is interrupted.
Pulse operation of fan
0: No pulse operation
1: Pulse operation when the thermostat does not call for refrigeration
2: Pulse operation when the thermostat does not call for refrigeration, but only
during night operation
Pulse operation period for fan
Here the overall pulse time is set. The sum of ON-to and OFF time.
ON time for fan
Here the % part of the period the fans are to be in operation is set.
Max. S4 temperature during defrost
Here the maximum S4 temperature during a defrost cycle can be set. If the value
is exceeded, the fans will be stopped. The function is not active when the thempera-
ture is set to max value (15°C).
Parameter for cooling function
Period time for the pulse width period (PWM)
Expert setting - The value should only be changed by specially trained staff.
Max. opening degree at PWM
Min. opening degree at PWM
Wind up factor at PWM
Expert setting - The value should only be changed by specially trained staff.
Amplification factor at PWM
Expert setting - The value should only be changed by specially trained staff.
Integration time at PWM
Expert setting - The value should only be changed by specially trained staff.
AK-CT 450A
User Guide RS8GR602 © Danfoss 2016-10
d27
Railh. at def
Defrost temp.
Def Start
Here you can start a manual defrost
Hold After Def
Shows ON when the controller is
operating with coordinated defrost.
Disable def.
Defrost in progress can be stopped
Defrost State
Status on defrost
1= pump down / defrost
MC def. start
The system unit can start/prevent
a defrost cycle
Fan control
F04
FanStopTemp.
F05
FanPulseMode
F06
Fan cycle
F07
Fan ON %
F22
FanStopS4Def
u59 Fan Relay
Here you can read the fan relay status,
or force-control the relay in "Manual
control" mode.
n63
Pwm Period
n64
Pwm Max. OD
n65
Pwm Min. OD
n66
PwmWindUpFac
n67
Pwm Kp fact.
n68
Pwm Tn sec
Forced cool.
(start of forced cooling)
Forced close
(forced stop of cooling)
23