Internal defrosting schedule/clock function
(Not used if an external defrosting schedule is used via data communication.)
Up to six individual times can be set for the defrost start throughout the day.
Defrost start, hour setting
Defrost start, minute setting (1 and 11 belong together, etc.)
When all t01 to t16 equal 0 the clock will not start defrosts.
Real-time clock::
In the event of a power failure of less than four hours, the clock function will be saved.
Clock: Hour setting
Clock: Minute setting
Clock: Date setting
Clock: Month setting
Clock: Year setting
Electricity monitoring
Current amount of electricity through relay 1
Same for relays 2 to 8
Fuse status for relay circuit 1, Off=interrupted, On=ok.
A broken fuse must be restored with the setting="On"
Same for relays 2 to 8
Set the electricity value at which the relay should cut out in the event of overcurrent
Recommended setting = measured consumption +25%. (In setting = 0 the current
monitor will be cancelled).
Same for relays 2 to 8
Current voltage at phase F1
Current voltage at phase F2
Current voltage at phase F3
Alarm limit for low DO2 load. (Not application 7)
An alarm is issued if the electricity consumption becomes lower than the set value.
Alarm limit for low DO5 load (Application 2,4 and 6 only)
Alarm limit for low DO6 load
Alarm limit for low DO8 load (Application 2, 3, 4 and 6 only)
Miscellaneous
Delay of output signal after start-up
After start-up or a power failure the controller's functions can be delayed so that
overloading of the electricity supply network is avoided.
Here you can set the time delay.
Digital input signal - DI1
The controller has a digital input 1 which can be used for one of the following
functions:
Off: The input is not used
1) Status display of a contact function
2) Door function. When the input is open it signals that the door is open. The
refrigeration and the fans are stopped and light switched on. When the time
setting in "A04" is passed, an alarm will be given. The cooling will restart when
the time in o89 has passed
3) Door alarm. When the input is open it signals that the door is open. When the time
setting in "A04" is passed, there will be alarm.
4) Defrost. The function is started with a pulse signal. (see also o37)
5) Main switch. Regulation is carried out when the input is short-circuited, and
regulation is stopped when the input is put in pos. OFF.
6) Night operation. When the input is short-circuited, there will be regulation for
night operation.
7) Thermostat band changeover. Switch to thermostat 2 (r21) when input is closed.
8) Separate alarm function. Alarm will be given when the input is short-circuited.
9) Separate alarm function. Alarm will be given when the input is opened. (For 8 and
9 the time delay is set in A27)
10) Case cleaning. The function is started with a pulse signal. See also description on
page 5.
11) Forced cooling(used for hot gas defrosting) when input is closed.
12) Night cover. Pulse signal activates night blind.
13) Not used.
14) Forced close when input is interrupted.
15) Appliance shutdown when input is closed.
16) Light. DO3 pulls when the input is closed.
17) Extra light. DO4 pulls when the input is closed.
18) Cancel defrost cycle. All defrost cycles are cancelled when the input is closed.
19) Override light (pulse signal)
24
User Guide RS8GR602 © Danfoss 2016-10
t01-t06
t11-t16
t07
t08
t45
t46
t47
L11
DO1 Amp
L12-18 DO2 Amp......DO8 Amp
L21
DO1 Fuse
L22-28 DO2 Fuse...... DO8 Fuse
L31
DO1 FuseSize
L32-38 DO2 FuseSize...... DO8 FuseSize
L51
L1 voltage
L52
L2 voltage
L53
L3 voltage
L62
DO2 Low Load
L65
DO5 Low Load
L66
DO6 Low Load
L68
DO8 Low Load
Miscellaneous
o01
DelayOfOutp.
o02
DI 1 Config.
Definition takes place with the nu-
merical value shown to the left.
(0 = off )
u10 DI1 state
(Measurement)
The DI input's present status is shown
here. ON or OFF.