22
POWERVALUE 11T IN — 1-3 KVA
4.6 LCD settings
WARNING!
Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or
bypass mode. Press and hold "Off/Enter" and "select" buttons for 5 seconds to switch LCD screen in
rack or tower display.
There are three parameters to set up the UPS.
Parameter 1: It's for program alternatives. Refer to below table.
Parameter 2 and parameter 3 are the setting options or values for each program.
01: Output voltage setting
Interface
02: Frequency converter enable/disable
Interface
03: Output frequency settings
Interface
Changing UPS settings might adversely impact the load supply or load functionality.
It is recommended to disconnect the load before proceeding
Settings
Parameter 3: Output voltage
You may choose the following output voltage:
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
Settings
Parameter 2: Enable or disable converter mode.
You may choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
Settings
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following outputfrequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz