3 G E T T I N G S TA R T E D
When using standard ABB EBMs, connect them
06 UPS Connect to EBM
according to Figure 6.
WARNING
06
3 2 4
Emergency Power Off (EPO) function is a
standard feature for the UPS. The EPO polarity is
configurable, and it is normally closed as a
default setting. If the connection between the
two ports of the EPO connector is disconnected,
EPO function will be active, and the UPS will stop
output power immediately.
3 2 4 1 Normally open
Normally the EPO connector is open on the rear
panel. Once the connector is closed with a wire, the
UPS will stop output until the EPO status is reset.
Disable EPO status
3 2 4 2 Normally closed
Normally the EPO connector is closed with a wire on
the rear panel. Once the connector is open, the UPS
will stop output until the EPO status is disabled.
Enable EPO status
WARNING—THE OUTPUT SOCKETS OF
THE UPS SYSTEM MAY STILL HAVE LIVE
ELECTRICAL CURRENT EVEN IF THE
POWER SUPPLY SYSTEM HAS BEEN
DISCONNECTED.

EPO Connection

Disable EPO status
Enable EPO status
13