POWERVALUE 11 RT G2 IN — 6-10 KVA

4.6 LCD settings

WARNING!
Press and hold select button for 5 seconds to enter UPS settings mode when UPS is in standby mode or
bypass mode. Press and hold "Off/Enter" and "select" buttons for 5 seconds to switch LCD screen in
rack or tower display.
There are two parameters to set up the UPS.
Parameter 1: It's for program alternatives. Refer to below table.
Parameter 2: The setting options or values for each program.
01: Output voltage setting
Interface
02: Frequency converter enable/disable
Interface
03: Output frequency settings
Interface
Changing UPS settings might adversely impact the load supply or load functionality.
It is recommended to disconnect the load before proceeding.
Settings
Parameter 1: Output voltage
Set up output voltage. You may choose the following output voltage:
208: output voltage is 208 Vac
220: output voltage is 220 Vac
230: output voltage is 230 Vac (default)
240: output voltage is 240 Vac
Settings
Parameter 1:
Enable or disable converter mode. You may choose from the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (default)
Settings
Parameter 1: Output frequency setting.
You may set the initial frequency on battery mode:
50: output frequency is 50 Hz
60: output frequency is 60 Hz
If converter mode is enabled, you may choose from the following output frequency:
50: output frequency is 50 Hz
60: output frequency is 60 Hz