Application planning

5.2 Installation location

5.2
Installation location
Selection of the installation site / mounting position
You can mount the PN/J1939 LINK either on a control panel or on a standard mounting rail:
Permitted mounting positions and permitted ambient temperature
The table below shows the permitted temperature range for the different mounting positions.
Mounting position
Horizontal
Vertical
Lying
Hanging
Ensure that condensation is not produced at a relative humidity between 10% and 95%.
Ensure that the atmospheric pressure is between 795 hPa and 1080 hPa. This corresponds
to an installation height of -1000 m to +2000 m.
PN/J1939 LINK is designed for natural heat dissipation by convection. Therefore observe
sufficient clearances:
● For horizontal mounting position: At least 35 mm above and below the PN/J1939 LINK
● For vertical mounting position: At least 35 mm left and right of PN/J1939 LINK
Provide sufficient space for connection of the supply voltage, Ethernet and J1939 bus.
28
Permitted ambient temperature
-25 ... +60 °C
-25 ... +55 °C
-25 ... +45 °C
-25 ... +45 °C
SIMATIC PN/J1939 LINK
Operating Instructions, 12/2018, A5E45307564-AA