Siemens SIMATIC PN/J1939 LINK Operating Instructions Manual page 61

Table of Contents

Advertisement

Module/submodule
for which the diag-
nostic information
is signaled
Manager
PGN input module
PGN input module
PGN input module
PROFINET inter-
face
SIMATIC PN/J1939 LINK
Operating Instructions, 12/2018, A5E45307564-AA
Channel diagnostics
error
Source address
changed - New address:
({1:d})
Received PGN message
had incorrect length -
({1:d}) bytes
PGN timeout -
({1:d})
DM1 data changed -
Source Address: ({1:d})
Internal software error -
({1:x})
10.2 Diagnostic messages to the S7 controller
Cause of error and possible solution
The configured "Source Address" is occupied. A new
valid address was set in the "Address Claiming"
process.
The configured address will be reloaded on device
restart.
Change the "Source Address" set in the module
parameters.
The PGN message was received, but it contains the
wrong number of data bytes. Data was partly dis-
carded.
Check the PGN parameter assignment.
PGN {1:d} was not received within the specified time.
Check the time for the programming PGN Reception
cycle.
DM1 message with different data was received from
source.
An internal error was detected and is signaled now,
i.e. after the module restart.
The error message disappears when you restart the
module again.
Diagnostics
59