Installation And Connection; Inserting The Et 200S Frequency Converter Into A Simotion Project - Siemens SIMATIC ET 200S Function Manual

Simotion supplement for the frequency converter
Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

2.3

Installation and connection

You must perform the following steps to be able to operate the ET 200S frequency converter
using the SIMOTION system:
1. Install and connect the ET 200S interface module (IM) with the components of the
ET 200S FC.
2. Establish the PROFIBUS connection between the IM and the SIMOTION device.
3. Set the PROFIBUS DP node address on the IM.
4. Switch on the terminating resistor at the first and last bus node.
Note
The commissioning of the ET 200S frequency converter can be performed either via
● the STARTER functionality integrated in the SIMOTION SCOUT engineering system
● or the STARTER engineering software.
For a description of commissioning and steps 1 to 4, see the SIMATIC
Frequency Converter Operating Instructions (03/2005 Edition).
5. Insert the ET 200S FC into the SIMOTION project (refer to Chapter Inserting the ET 200S
frequency converter into a SIMOTION project (Page 11)).
6. Parameterizing the ET 200S FC.
To parameterize the module, go to HW Config. Double-click the relevant module to open
the Properties dialog box. Select the Parameters tab to access the parameterization
interface. There you can assign parameters for your module.
See the SIMATIC
Edition).
7. Link the function block to the SIMOTION project (refer to Chapter Integrating the function
block in the user project (Page 13)).
2.4

Inserting the ET 200S frequency converter into a SIMOTION project

Requirement
The following requirements must be met:
1. You have created a project in SIMOTION SCOUT and inserted a rack with a SIMOTION
device in the hardware configuration.
2. You have configured a PROFIBUS subnet.
Note
For how to create a project and configure a PROFIBUS subnet, refer to the online help of
SIMOTION SCOUT.
Supplement for the ET 200S frequency converter
Function Manual, 01/2015
2.4 Inserting the ET 200S frequency converter into a SIMOTION project
(via "Insert single drive"), or
ET 200S FC Frequency Converter Operating Instructions (03/2005
Description
ET 200S FC
11