Replacing A Ld 800 Hse Ex By A New Ld 810Hse Ex - ABB Ability 800xA Series User Manual

Device management foundation fieldbus
Hide thumbs Also See for Ability 800xA Series:
Table of Contents

Advertisement

2 Hardware Installation

2.9 Replacing a LD 800 HSE Ex by a New LD 810HSE Ex

7.
The second Linking Device will take over the configuration data from the primary
device and will start operation in the role "Secondary". For indication of proper
operation as a secondary device, refer to
8.
Configure the Linking Device redundancy with the configuration tool (Fieldbus Builder
FOUNDATION™ Fieldbus) and - if an OPC Server FOUNDATION™ Fieldbus is
used - download the OPC server.
2.9
Replacing a LD 800 HSE Ex by a New LD 810HSE Ex
Do not combine different module types in redundant pairs, i.e. do not combine a
Linking Device of type LD 810HSE Ex with other types such as LD 800HSE or
LD 800HSE Ex. If one of the redundant LD 800HSE pair fails and in order not to affect
the running plant, replace the defective LD 800HSE Ex with a new LD 800HSE Ex
as mentioned in
Devices on page
When replacing a set of redundant LD 800HSE Ex with a set of redundant
LD 810HSE Ex, both Linking Devices of a set need to be removed and replaced. This
will affect the corresponding FOUNDATION™ Fieldbus devices and can affect the
running plant.
When a non-redundant LD 800HSE Ex needs to be replaced with a LD 810HSE Ex,
please follow the replacement steps as given below.
1.
Before connecting the new LD 810HSE Ex, assign the new LD 810HSE Ex the same
IP address and subnet mask as the replaced LD 800HSE Ex, for details see
Configuration on page
2.
Remove the power terminal block from the old LD 800HSE Ex.
3.
Remove the redundancy link wiring and the Ethernet cable from the old
LD 800HSE Ex.
4.
If not indicated on the cable, make a note to which channel each H1 link is connected.
Then remove the H1 terminal blocks.
5.
Replace the old LD 800HSE Ex by the new LD 810HSE Ex that has been assigned
the same IP address and subnet mask as the replaced LD 800HSE Ex.
6.
Plug in the H1 terminal blocks to the new LD 810HSE Ex. It is recommended to
connect the H1 segments to the new LD 810HSE Ex at the same positions as on
the replaced LD 800HSE Ex.
2PAA114135-610
Replacing a Defective Linking Device in a Redundant Set of Linking
46.
62.
Status Indicators - LEDs on page
37.
Network
48