3 Configuration
3.3 Plant Configuration and Commissioning
3.3.3

Speed up of Device Assignment

The time needed for an H1 device address assignment can be configured for dynamic
adaption to the speed of the H1 device. Set parameter "T3" of an individual H1 link as
follows:
"T3 = 0 s": to enable the dynamic adaption
"T3 = 45 s": to disable dynamic adaption by reverting to this default value, in case
that the address assignment cannot be performed properly for an individual H1
device.
For details on the configuration and commissioning of FF subsystems in general and
specially of Linking Devices, refer to the System 800xA - Device Management,
FOUNDATION™ Fieldbus Configuration (3BDD012902*) manual or the Engineering
Reference Manual Communications and Fieldbusses for AC 800F.