2 Hardware Installation
2.4 Mounting and Dismounting
FF H1 Bus Line Channel 3
Table 2.11: H1 Channel 3 Connections
CH3
FF H1 Bus Line Channel 4
Table 2.12: H1 Channel 4 Connections
CH4
The fieldbus shield is not directly connected to functional earth. For EMC reasons, it
is only connected via a capacitor. If a direct connection to functional earth or protective
earth is required, you need to implement this separately.
2PAA114135-610
Pin
Signal
13
+
Fieldbus +
14
S
Fieldbus shield
15
-
Fieldbus -
Pin
Signal
16
+
Fieldbus +
17
S
Fieldbus shield
18
-
Fieldbus -
Description