Availability Of D U /D T Filter And Common Mode Filter By Drive Type; Additional Requirements For Explosion-Safe (Ex) Motors; Hx_ And Am; Additional Requirements For Braking Applications - ABB ACS880-04 Hardware Manual

Drive modules
Hide thumbs Also See for ACS880-04:
Table of Contents

Advertisement

Availability of d u /d t filter and common mode filter by drive type

Product type
ACS880-04

Additional requirements for explosion-safe (EX) motors

If you use an explosion-safe (EX) motor, obey the rules in the requirements table above.
In addition, consult the motor manufacturer for any further requirements.
Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and
AM_
Use the selection criteria given for non-ABB motors.

Additional requirements for braking applications

When the motor brakes the machinery, the intermediate circuit DC voltage of the drive
increases, the effect being similar to the motor supply voltage increasing by up to
20 percent. Consider this voltage increase when specifying the motor insulation
requirements if the motor will be braking a large part of its operation time.
Example: Motor insulation requirement for a 400 V AC line voltage application must
be selected as if the drive were supplied with 480 V.

Additional requirements for ABB high-output and IP23 motors

The rated output power of high output motors is higher than what is stated for the
particular frame size in EN 50347 (2001).
This table shows the requirements for protecting the motor insulation and bearings
in drive systems for ABB random-wound motor series (for example, M3AA, M3AP and
M3BP).
Nominal AC supply
voltage
Motor insulation
U
≤ 500 V
Standard
n
500 V < U
≤ 600 V
Standard
n
or
Reinforced
600 V < U
≤ 690 V
Reinforced
n

Additional requirements for non-ABB high-output and IP23 motors

The rated output power of high-output motors is higher than what is stated for the
particular frame size in EN 50347 (2001).
If you plan to use a non-ABB high-output motor or an IP23 motor, consider these
additional requirements for protecting the motor insulation and bearings in drive
systems:
Guidelines for planning the electrical installation 81
Availability of du/dt filter
Ordered separately, see
ters (page 261)
ABB d u /d t and common mode filters, insulated N-end motor
system
P
n
P
n
-
+ d u /d t
-
+ d u /d t
Availability of common mode filter
d u /d t fil-
Requirement for
bearings
100 kW ≤ P
< 100 kW
200 kW
< 140 hp
140 hp ≤ P
268 hp
+ N
+ d u /d t + N
+ N
+ d u /d t + N
(CMF)
+E208
P
<
≥ 200 kW
n
n
<
P
≥ 268 hp
n
n
+ N + CMF
+ d u /d t + N + CMF
+ N + CMF
+ d u /d t + N + CMF