2 Hardware Installation
2.4 Mounting and Dismounting
2.3.3
Hazardous Location - European and International Approval (ATEX,
IECEx)
The equipment was assessed as based on the following standards and editions:
a) IEC 60079-0:2011 Ed. 6, modified Cor. 2012 + Cor. 2013 / EN 60079-0:2012 +
A11:2013
b) IEC 60079-11:2011 Ed. 6 + Corr. 2012 / EN 60079-11:2012
c) IEC 60079-15:2010 Ed. 4 / EN 60079-15:2010
If indicated on the device label or by technical documentation, the LD 810HSE Ex is
suitable for use in gas Ex atmospheres of Zone 2 in the explosion groups IIA, IIB, and
IIC in temperature class T4, if accommodated in a tested enclosure.
•
IECEx marking for explosion protection: Ex nA [ic] IIC T4 Gc
•
ATEX marking for explosion protection:
The Ex protection method [ic] corresponds only to the FF-H1 fieldbus interfaces.
The LD 810HSE Ex complies with the applicable standards and regulations and meets
the requirements of Directive 2014/34 EU. The requirements for mounting the device as
part of the system in potentially explosive atmospheres (e. g. IEC/EN 60079-14) must
be strictly adhered to.
Certificates
•
ATEX
The EC type examination number for ATEX is: BVS 15 ATEX E 121 X
•
IECEx
The type examination number for IECEx is: IECEx BVS 15.0101X
For general requirements, rules for installing, commissioning, maintaining, and the
appropriate use of the LD 810HSE Ex in hazardous atmospheres, refer to
2.4
Mounting and Dismounting
Installation and inspection tasks are to be carried out by qualified personnel only, i.e.
personnel qualified according to TRBS 1203 or similar. The definition of terms can
be found in IEC 60079-17.
Make sure the LD 810HSE Ex is mounted in a manner that the power supply
disconnecting device or interrupt facility can always be reached easily.
2PAA114135-610
II 3G nA [ic] IIC T4 Gc
Appendix
C.
28