2 Hardware Installation
2.4 Mounting and Dismounting
To maintain the operating temperature of the Linking Device, ensure that proper ventilation
is maintained in the enclosure:
Depending on the installation position, different ambient operating temperatures are
allowed.
Clearance between the Linking Device and the adjacent components or side walls
of the housing must be adhered to as illustrated in
Figure 2.2: LD 810HSE Ex Horizontal Installation Position
Provide a minimum space of 50 mm to the air inlet or air outlet.
Table 2.4: LD 810HSE Ex Maximum Ambient Operating Temperature for Horizontal
Installation
Maximum number
of fieldbus
channels used
The maximum permissible ambient temperature values are also valid for a 180°
rotated installation position.
2PAA114135-610
Maximum fieldbus
voltage
4
32 V DC
2
24 V DC
4
32 V DC
2
24 V DC
Figure
2.2.
Minimum distance
0 mm
0 mm
17.5 mm
17.5 mm
Maximum
permissible
ambient
temperature T
a
55 °C
60 °C
65 °C
70 °C