Siemens LOGO!Power Series Operating Instructions Manual page 46

Table of Contents

Advertisement

Ambient conditions
Damaging gases
Atmospheric pressure
46
6EP1311-1SH03 (5 V / 3 A)
6EP1311-1SH13 (5 V / 6.3 A)
6EP1321-1SH03 (12 V / 1.9 A)
6EP1322-1SH03 (12 V / 4.5 A)
6EP1351-1SH03 (15 V / 1.9 A)
6EP1352-1SH03 (15 V / 4 A)
6EP1331-1SH03 (24 V / 1.3 A)
6EP1332-1SH43 (24 V / 2.5 A)
6EP1332-1SH52 (24 V / 4 A)
Tested according to:
EN 60068-2-42Sulfur dioxide: 10 cm
EN 60068-2-43Hydrogen sulfide: 1 cm
Operation:
1080 ... 795 hPa (-1000 ... +2000 m)
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-2 Mounting height derating (Page 19)
Overvoltage category:
III up to 2000 m (EN 50178)
II from 2000 m up to 6000 m (EN 50178)
Storage:
1080 ... 660 hPa (-1000 ... +3500 m)
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
/m
, 4 days
3
3
/m
, 4 days
3
3
LOGO!Power

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents