Technical Data; Input - Siemens LOGO!Power Series Operating Instructions Manual

Table of Contents

Advertisement

Technical data

Note
For an AC input voltage, the technical data is applicable for rated input voltage, rated load
and +25° C ambient temperature (if nothing else is specified).
6.1

Input

Input
Rated voltage
U
e rated / for AC
Voltage range / for AC
Input voltage / for DC
Wide-range input
Overvoltage
resistance
Mains buffering at
Ia rated, min.
Mains buffering
Rated line frequency
Line frequency range
Input current / at rated
value of input voltage
120 V
Input current / at rated
value of input voltage
230 V
Switch-on current
limitation (+ 25° C),
max.
I²t, max.
Built-in line-side fuse
Protection in the line
feeder cable (IEC 898)
LOGO!Power
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
6EP1311-1SH03
6EP1311-1SH13
(5 V / 3 A)
(5 V / 6.3 A)
1-phase AC or DC
100...240 V
85...264 V
110...300 V
Yes
2.3 x Ue rated, 1.3 ms
40 ms
40 ms
at Ue = 187 V
50/60 Hz
47...63 Hz
0.36 A
0.71 A
0.22 A
0.37 A
26 A
50 A
0.8 A²·s
3 A²·s
Internal
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A
6EP1321-1SH03
6EP1322-1SH03
(12 V / 1.9 A)
(12 V / 4.5 A)
40 ms
40 ms
0.53 A
1.13 A
0.3 A
0.61 A
25 A
55 A
0.8 A²·s
3 A²·s
6
6EP1351-1SH03
(15 V / 1.9 A)
40 ms
0.63 A
0.33 A
25 A
0.8 A²·s
27