Error Indications
9-1
Display During Equipment Error
This controller has a display function to indicate several types of error code shown below. If any
of the error code is displayed, please eliminate the cause of error immediately. After the cause
is eliminated, turn off the power once, and then re-start the controller.
Display
Possible cause
"
"
q Thermocouple burnout.
UUUU
w Resistance bulb sensor (A) burnout.
e PV exceeds upper limit of the range by 5%FS.
q Resistance bulb sensor B or C wire burnout.
"
LLLL
"
w Resistance bulb sensor (between A & B or A &
C) short.
e PV is below lower limit of the range by 5%FS.
r Burnout or short in the voltage input.
q PV < -199.9
"
LLLL
"
"
Err
"
Incorrect setting (Pvb/PvF)
(SV flickers)
q H'4000 is added into the dP30 set value
PV is not
displayed
w SbMd set value is set at 4 to 7, and STbY is ON
q H'2000 is added into the dP30 set value
SV is not
w SbMd set value is set at 4 to 7, and STbY is ON
displayed
q Check the settings of dP01 to dP30
Parameters
w Check the password function
may not be
displayed
Note) The error display does not appear even when it must appear depending on the setting
of parameter SbMd ("
S S S S E E E E T T T T C C C C h h h h 6 6 6 6
").
10
Input Range and Codes (standard range)
Measurement
Input type
range [°C]
Resistance bulb
Pt 100Ω
0 to 150
JIS (IEC)
0 to 300
0 to 500
0 to 600
-50 to 100
-100 to 200
-150 to 600
-200 to 850
Thermocouple
J
0 to 400
0 to 1000
K
0 to 400
0 to 800
0 to 1200
R
0 to 1600
B
0 to 1800
S
0 to 1600
T
-200 to 200
-200 to 400
E
0 to 800
-200 to 800
N
0 to 1300
PL-
2
0 to 1300
DC voltage
0 to 5V DC
-1999 to 9999 (Range where scaling is allowed)
1 to 5V DC
0 to 10V DC
2 to 10V DC
0 to 100mV DC
DC current
0 to 20mA DC
4 to 20mA DC
Note 1 : For DC current input, attach a 250Ω resistance to convert the range to 1 to 5V or 0 to
5V DC.
Note 2 : Input accuracy is ±0.3% FS ± 1 digit ± 1°C or 2°C whichever greater.
Except,
B thermocouple 0 to 400°C: ±5% FS ± 1 digit ± 1°C
R thermocouple 0 to 500°C: ±1% FS ± 1 digit ± 1°C
T thermocouple -200 to -150°C: ±0.5% FS ± 1 digit ± 1°C
Note 3 : Input accuracy cannot be ensured when using an input smaller than the minimum
range.
Control output
Output as setting value when
an error occurs
(set in parameter Flo1 or
Flo2)
Normal control
* The controller does not have
to be restarted
Normal control
* The controller does not have
to be restarted
Normal control
* The controller does not have
to be restarted
Measurement
Smallest input
Input code
range [°F]
increment °C
1 1 1 1
32 to 302
0.1
"
"
32 to 572
0.1
32 to 932
0.1
32 to 1112
1
-58 to 212
0.1
-148 to 392
0.1
-238 to 1112
1
-328 to 1562
1
2 2 2 2
32 to 752
0.1
"
"
32 to 1832
1
3 3 3 3
32 to 752
0.1
"
"
32 to 1472
0.1
32 to 2192
1
4 4 4 4
32 to 2912
1
"
"
5 5 5 5
32 to 3272
1
"
"
6 6 6 6
32 to 2912
1
"
"
7 7 7 7
-328 to 392
0.1
"
"
-328 to 752
0.1
8 8 8 8
32 to 1472
0.1
"
"
-328 to 1472
1
1 1 1 1 2 2 2 2
32 to 2372
1
"
"
1 1 1 1 3 3 3 3
32 to 2372
1
"
"
"
1 1 1 1 5 5 5 5
"
"
1 1 1 1 6 6 6 6
"
"
1 1 1 1 7 7 7 7
"
"
1 1 1 1 8 8 8 8
"
"
1 1 1 1 9 9 9 9
"
"
1 1 1 1 5 5 5 5
"
"
1 1 1 1 6 6 6 6
"
11
Alarm Action Type Codes
Type
DO1 to DO3
0
Absolute value
1
alarm
2
3
4
Deviation alarm
5
6
7
8
9
10
Zone alarm
11
12

(Note1)

13
(Note1)
14
(Note1)
15
(Note1)
Dual Set Value Alarm Codes
Type
DO1 to DO3
High/Low limit
16
alarm
17
18
19
20
21
22
23
– 18 –
Alarm Type
Action diagram
No alarm
High alarm
PV
ALn
Low alarm
PV
ALn
High alarm (with hold)
PV
ALn
Low alarm (with hold)
PV
ALn
High alarm
PV
SV
Low alarm
PV
SV
High/Low alarm
PV
SV
High alarm (with hold)
PV
SV
Low alarm (with hold)
PV
SV
High/Low alarm (with hold)
PV
SV
High/Low deviation alarm
PV
SV
High/Low absolute alarm
PV
High/Low deviation alarm
PV
SV
High absolute/Low
PV
deviation alarm
SV
High deviation/Low
PV
absolute alarm
SV
Alarm Type
Action diagram
High/Low absolute alarm
PV
High/Low deviation alarm
PV
SV
High absolute/Low
PV
deviation alarm
SV
High deviation/Low
PV
absolute alarm
SV
High/Low absolute alarm
PV
(with hold)
High/Low deviation alarm
PV
(with hold)
SV
High absolute/Low
PV
deviation alarm (with hold)
SV
High deviation/Low
PV
absolute alarm (with hold)
SV
t
t
t
t
ALn
t
ALn
t
ALn
ALn
t
ALn
t
ALn
ALn
t
AL1
AL2
t
AL1
AL2
t
AL1
AL2
t
AL1
AL2
t
ALnh
ALnL
t
ALnh
ALnL
t
ALnh
ALnL
t
ALnh
ALnL
t
ALnL
ALnL
t
ALnh
ALnL
t
ALnh
ALnL
t
ALnh
ALnL
t

Advertisement

loading