Installing system components
3.6 Connecting the connection box
Connect the connection box in the following sequence:
1. Functional grounding
2. Power supply
3. Control via PROFINET (LAN)
4. Other Ethernet devices, such as an additional connection box
3.6.2

Opening and closing connection box standard and connection box advanced

The connection boxes standard and advanced must be opened for connecting and setting
the box ID. To avoid damage to the connection box, read the information in the section
"General safety instructions (Page 31)" about working in and on electrical systems and about
ESD.
Requirement
● The connection box is de-energized.
● Torque screwdriver with T10 insert
Procedure
Open
1. Loosen the 4 screws
2. Lift the cover
3. Remove the screws and the cover.
60
Cover
Screws
Screw glands M16x1.5 for cable diameters 5 to 10 mm
.
carefully, because the seal may stick to the lid and can be pulled out.
Mobile Panels 2nd Generation
Operating Instructions, 09/2018, A5E33876626-AC