11.11.2
Fast connector X1 and X2
Fast Connector, 4-pin
The connection box contains two fast connectors for connecting the Ethernet data cables.
Only relevant if the PLC is connected directly to the connection box.
1
11.11.3
Plug-in terminal strip X10
Plug-in terminal strip, 12-pin
Mobile Panels 2nd Generation
Operating Instructions, 09/2018, A5E33876626-AC
11.11 Interfaces of the connection box standard and connection box advanced
Contact
Color
1
Yellow
2
White
3
Orange
4
Blue
Contact
Assignment
1
Functional grounding
2
3
P24
4
Not connected
5
STOP 13
6
STOP 14
7
STOP 23
8
STOP 24
9
ENABLE2+
10
ENABLE1–
11
ENABLE1+
12
ENABLE2–
Assignment in the connection box
RD+
TD+
RD–
TD–
Associated circuits and reference information
Ground and power supply
See "Connecting the functional grounding and power
M
supply to the connection box (Page 64)."
Emergency stop / stop button
See section "Pressing the emergency stop / stop
button (Page 83)" and wiring information in the
following section
Enabling button
See section "Operating the enabling button (Page 81)"
and wiring information in the following section
Technical specifications
Assignment in the PLC
1
TD+
RD+
TD–
RD–
249