Parameterizing the Mobile Panel

5.10 Enabling PROFINET

10. Confirm your entries with "OK".
The dialog closes.
The list of certificates on the HMI device is updated.
5.10
Enabling PROFINET
The HMI device communicates with the PLC over Ethernet. PROFINET must be enabled
before you can use the following functions:
● Fail-safe operation with emergency stop/stop button and enabling button over PROFIsafe
● Use of PROFINET direct keys
Requirement
The Control Panel is open.
Procedure
1. Open the "Profinet" dialog using the "PROFINET" icon.
2. Select the "PROFINET IO enabled" check box.
3. Enter the PROFINET device name of the HMI device.
126
Enables or disables the PROFINET IO direct keys
Text box for the device name
MAC address of the HMI device
NOTICE
Device name must correspond to HW Config
If the device name does not match the device name entered in the HW Config of
STEP 7, the project will start without PROFIsafe connection. Use the device name from
the HW Config of STEP 7.