Compatibility with Conventional Models

7.2 Analog Output Unit

7.2.1 Compatibility with Conventional Models
 Specification Comparison Chart
Item
Appearance
DIP switch
Terminal block
Resolution and Operation mode
Number of channels
Analog output range
-10 to 10 V DC
-5 to5 V DC
Analog output
voltage range
0 to 10 V DC
0 to 5 V DC
0 to 20 mA
Analog input
current range
4 to 20 mA
Conversion speed
Voltage
Overall
precision
Current
External power
supply
Power supply
Control unit
(24V DC)
consumption current
increment
(Note 1):The resolution and operation mode is switched by the mode switch.
(Note 2):When selecting the 14-bit mode, the range can be set for each channel separately by user programs. Also,
the ranges of -5 to +5V DC, 0 to 10V DC and 0 to 20 mA DC can be set by user programs only when selecting
the 14-bit mode.
7-4
FP0-A04V/ FP0-A04I
None
1
12-bit (1/4000)
4 ch
Voltage/Current (Each model)
Available (FP0-A04V)
Not available
Not available
Not available
Not available
Available (FP0-A04I)
500 μs / channel
±0.6%F.S. or less (at 25°C)
±1%F.S. or less (at 0 to 55°C)
100 mA or less (FP0A04V)
130 mA or less (FP0A04I)
20 mA or less
FP0RDA4
Equipped
2 (For voltage output / For current
output)
12-bit (1/4000)
14-bit (1/16000) (Note 1)
4 ch
Voltage/Current
(Built in one unit)
Available (Note 2)
Available (Note 2)
Available (Note 2)
Available (Note 2)
Available (Note 2)
Available (Note 2)
500 μs / All channels
±0.2%F.S. or less (at 25°C)
±0.4%F.S. or less (at 0 to 55°C)
±0.3%F.S. or less (at 25°C)
±0.6%F.S. or less (at 0 to 55°C)
180 mA or less
10 mA or less