2.2.2 Setting of Mode Switch

 Setting of the mode switch
Item
No.
Resolution
1
2
3
Output switch
4
5
(Note 1): In the 14-bit mode, the output range is set by writing into the operation memory WY with a user program.
(Note 2): For the both FP0-A04V/A04I compatibility 12-bit mode and 14-bit mode, the output can be selected for each
channel.
(Note 3): All the switches are set to OFF at the factory.
(Note 4): The switch settings will be valid when the power is turned ON from OFF. The settings will not change if the
operation power supply is switched when it is ON.
KEY POINTS
In the FP0-A04V/A04I compatibility 12-bit mode, the voltage output range is
-10 to +10 V, and the current output range is 4 to 20 mA.
Settings
OFF:FP0-A04V/A04I compatible 12-bit mode, ON:14-bit mode (Note 1)
CH0
CH1
OFF:Voltage output
ON:Current output (Note 2)
CH2
CH3
2.2 Analog Output Unit (FP0R-DA4)