Setting Of Averaging Processing; Enabling Averaging Processing - Panasonic FP0R Series User Manual

Analog i/o unit
Hide thumbs Also See for FP0R Series:
Table of Contents

Advertisement

Analog Input Averaging Processing

5.2 Setting of Averaging Processing

5.2.1 Enabling Averaging Processing

The averaging processing can be set by the following methods.
 12-bit FP0-A80 compatibility mode / FP0-A21 compatibility mode
The averaging processing is enabled only when the mode switch No.5 of the unit is ON.
• The averaging method of all channels is the moving average 10 times (Max. and min.
removal).
 14-bit mode
• The averaging processing is enabled only when the mode switch No.5 of the unit is ON.
• The default is the moving average 10 times (Max. and min. removal).
• It is possible to specify the averaging method (Moving average 10 times / No. of averaging
times: 64 / No. of averaging times: 128 / No averaging) by a user program for each channel.
REFERENCE
For details of the setting method of the mode switch, refer to the chapter 2
"Names and Functions of Parts".
For details of the programming method for the analog input unit (FP0R-
AD4/AD8), refer to "4.2.2 Setting of Input Range and Averaging Processing
(14-bit Mode Only)".
For details of the programming method for the analog I/O unit (FP0R-
A21/A42), refer to PAGEREF"4.4.5 Switching of Input Range and Averaging
Method (14-bit Mode Only)".
5-4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp0rad4Afp0rad8Afp0ra21Afp0ra42Afp0rda4

Table of Contents