Output Conversion Characteristics (Voltage Range) - Panasonic FP0R Series User Manual

Analog i/o unit
Hide thumbs Also See for FP0R Series:
Table of Contents

Advertisement

Creating Programs

4.5.3 Output conversion Characteristics (Voltage Range)

 -10V to 10V DC output
Conversion characteristic
 -5V to 5V DC output (14-bit mode only)
Conversion characteristic
KEY POINTS
The following operations are performed when a value exceeding the
allowable range is written. Always insert a program for checking the upper
and lower limits right before a program for writing data.
Mode
Data range
-2049 or less
12-bit
mode
-2048 to -2001
-8193 or less
14-bit
mode
-8192 to -8001
4-40
Correspondence table of D/A Conversion values
12-bit
-2000
-1000
0
1000
2000
Processing if the range is exceeded
Digital input value
-2001 or less
2001 or more
Correspondence table of D/A Conversion values
Processing if the range is exceeded
Digital input value
Description
The bits D and C of a written value may be regarded as
2048 or more
channel switching flags and converted to an unintended
value and output.
The value does not change and the previous value is
2001 to 2047
held.
The bits F and E of a written value may be regarded as
8192 or more
channel switching flags and converted to an unintended
value and output.
The value does not change and the previous value is
8001 to 8191
held.
Digital value
14-bit
-8000
-4000
0
4000
8000
-8001 or less
8001 or more
Digital value
14-bit
-8000
-4000
0
4000
8000
-8001 or less
8001 or more
Output voltage (V)
-10.0
-5.0
0.0
5.0
10.0
Output voltage (V)
Refer to the following
notes.
Output voltage (V)
-5.0
-2.5
0.0
2.5
5.0
Output voltage (V)
Refer to the following
notes.