When a Com Module is added to expansion slot #3, the dual 4-20mA
outputs acquire the identification letters I and J. These are the letter
assignments for any card installed in this slot.
If the dual 4-20mA input driver is installed onto the Com Module, it is
represented by the letters K and L.
The Dual 4-20mA input driver card is the only card that can be added
to the Com Module.
The Wiring Terminal Table shows all connections to the Com Module
Wiring Terminal Table:

Component Function

XT1
Modbus RTU Master to ext. Slave
(For Pyxis)
XT2
Modbus RTU Slave to ext. Master
For Gateways and direct connection
XA1
mA output Channel 1
XA2
mA output Channel 2
XB11
Modbus RTU Master to ext. Slave
XB12
Modbus RTU Master to ext. Slave
XB21
Modbus RTU Slave to ext. Master
XB22
Modbus RTU Slave to ext. Master
XE1
mA input Channel 1
XE2
mA input Channel 2
Driver card installed on Com module
Description
Connection
resistor jumpers
Def: Failsafe
resistor jumpers
Default: Standard?
Pin 1 = (-)
Pin 2 = (+)
Pin 1 = (-)
Pin 2 = (+)
Pin 1 = (A)
Pin 2 = (B)
Pin 3 = (GND)
Pin 1 = (shield)
Pin 2 = (+24)
Pin 1 = (A)
Pin 2 = (B)
For Daisy chain
Pin 3 = (GND)
Pin 4 = (shield)
(optional driver)
Pin 1 = (GND)
Pin 2 = (mA input)
Pin 3 = (+23)
(optional driver)
Pin 1 = (GND)
Pin 2 = (mA input)
Pin 3 = (+23)
2 4 6
Failsafe termination
1 3 5
2 4 6
Standard termination
or SW control
1 3 5
2 4 6
No termination
(park position)
1 3 5
Page 5 of 30