System Application Guide
Spec. No. 582127000 (Model 721
List BG: Battery Disconnect Distribution Panel,
(4) TPH Fuse Battery Disconnect Positions (without Shunts) (without Return Busbar)
Features
(4) -48V Battery Disconnect Fuse Mounting Positions:
70A to 400A TPH Type Fuses.
Does NOT include Shunts.
Does NOT include a Return Busbar.
1200A Maximum Capacity.
Restrictions
Cannot be used with List 21.
Must be installed in top row only (limit one battery disconnect panel per distribution cabinet).
Maximum lug width, 1.75 inches.
Ordering Notes
1) Order fuses as required per
2) Order load lugs (two hole, 3/8" bolt clearance hole, 1" centers) as required for each distribution position
per
Table
28.
3) Order lug hardware kit (P/N 548184) as required. Lug hardware kit provides sixteen (16) sets of 3/8-16
hardware (bolts, flat washers, and lock washers), enough for eight (8) lug landing points.
BATTERY CONNECTIONS
3/8-16 Captive Nuts on 1" Centers
(Customer must supply
or order additional
hardware)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NPBB
Table
15. Order replacement alarm fuses (1/4A) per
Battery
Connections
Page 45 of 125
Issue AF, February 26, 2014
Maximum Lug Width: 1.7 5 inches.
SAG582127000