KEB COMBIVERT R6 Instruction Manual page 13

Power supply and regenerative unit
Hide thumbs Also See for COMBIVERT R6:
Table of Contents

Advertisement

The COMBIVERT R6 is conditionally short-circuit proof (VDE 0160). After re-
setting the internal protection devices, the function as directed is guaranteed.
Exception:
Earth fault or short circuits at the output in regenerative operation can lead
Condition-
to a defect in the unit.
ally short-
circuit proof
If earth fault or short circuits occur in power supply operation, semi-conduc-
tor protection is only limited.
With applications requiring the COMBIVERT R6 to be switched on and off cycli-
cally, maintain an off-time of at least 5 min. If you require shorter cycle times
Cyclic acti-
please contact KEB. Switching off during the initialization phase can cause
vation and
undefined conditions.
deactiva-
tion
When using systems with RCD, the instructions or the requirements of VDE
RCD (resid-
0100 -T 530 (IEC 60364-5) must be observed. The recommended tripping cur-
ual current
rent of RCD type "B" is 300 mA.
operated
circuit-
breaker)
Safety Instructions
GB - 13