Markings
Special Conditions for Safe Use (X):
1.When installed as Division 2 equipment, the Model 1410 Smart Wireless
Gateway shall be mounted within a tool-secured enclosure which meets the
requirements of ANSI/ISA 61010-1 and be capable of accepting the applicable
wiring methods per the NEC.
Canada
N6 Canada Division 2
Certificate 2646342 (CSA)
Standards CAN/CSA C22.2 No. 0-10, CSA C22.2 No. 213-M1987 (R2013),
Markings
Shall be powered by a class 2 power supply.
Suitable for dry indoor locations only.
Equipment must be installed in a suitable tool accessible enclosure subject
to the end use application.
Using the 1410H and the 781 Field Links in a hazardous location requires
barriers between the two units.
Europe
N1 ATEX Type n
Certificate Baseefa14ATEX0125X
Standards
Markings
Special Conditions for Safe Use (X):
1. The equipment must be installed in an area of not more than Pollution
Degree 2 as defined in IEC 60664-1, and in an enclosure that provides a
degree of protection of at least IP54 and meets the relevant requirements of
EN 60079-0 and EN 60079-15.
2. External connections to the equipment must not be inserted or removed
unless either the area in which the equipment is installed is known to be non-
hazardous, or the circuits connected have been de-energised.
24
NI CL 1, DIV 2, GP A, B, C, D T4; Suitable for use in CL II, III, DIV 2,
GP F, G T4; T4(-40 °C ≤ Ta ≤ 60 °C);
CSA C22.2 No. 61010-1 – 2012, ANSI/ISA-12.12.01 – 2012,
rd
UL61010-1, 3
Edition
Suitable for CL I, DIV 2, GP A, B, C, D; T4 (-40 °C ≤ Ta ≤ 70 °C)
EN 60079-0: 2012, EN 60079-15: 2010
II 3 G Ex nA IIC T4 Gc, T4(-40 °C ≤ Ta ≤ +75 °C), V
February 2019
= 30Vdc
MAX
Emerson.com/Rosemount