11.2 STEEL FINISHING MOUNTING
1
2
4
3

12. ELECTRICAL CONNECTIONS

The instruments are provided with screw terminal block to connect cables with a cross section up to
2,5 mm
for the digital and analogue inputs. Relays and power supply have a Faston connection
2
(6,3mm). Heat-resistant cables have to be used. Before connecting cables make sure the power
supply complies with the instrument's requirements. Separate the probe cables from the power
supply cables, from the outputs and the power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
12.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid
infiltration. It is recommended to place the thermostat probe away from air streams to correctly
measure the average room temperature.
13. HOW TO USE THE HOT KEY
13.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
2.
When the controller is ON, insert the "Hot key" and push o key; the "uPL" message
appears followed a by flashing "End"
3.
Push "SET" key and the End will stop flashing.
4.
Turn OFF the instrument remove the "Hot Key", then turn it ON again.
NOTE: the "Err" message is displayed for failed programming. In this case push again o key if you
want to restart the upload again or remove the "Hot key" to abort the operation.
13.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY
(DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed "Hot Key" into the 5 PIN receptacle and then turn the Controller ON.
3.
Automatically the parameter list of the "Hot Key" is downloaded into the Controller memory,
the "doL" message is blinking followed a by flashing "End".
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the "Hot Key"..
NOTE the message "Err" is displayed for failed programming. In this case turn the unit off and then
on if you want to restart the download again or remove the "Hot key" to abort the operation.

14. ALARM SIGNALS

Message
Cause
"P1"
Room probe failure
"P2"
Second probe failure
"P3"
Third probe failure
"P4"
Fourth probe failure
"HA"
Maximum temperature alarm
"LA"
Minimum temperature alarm
"HA2"
Condenser high temperature
"LA2"
Condenser low temperature
"dA"
Door open
"EA"
External alarm
"CA"
Serious external alarm (i1F=bAL) All outputs OFF.
"CA"
Pressure switch alarm (i1F=PAL) All outputs OFF
14.1 SILENCING BUZZER / ALARM RELAY OUTPUT
If "tbA = y", the buzzer and the relay are is silenced by pressing any key.
If "tbA = n", only the buzzer is silenced while the alarm relay is on until the alarm condition recovers.
14.2 ALARM RECOVERY
Probe alarms P1", "P2", "P3" and "P4" start some seconds after the fault in the related probe; they
automatically stop some seconds after the probe restarts normal operation. Check connections
before replacing the probe.
1592027000 XW10L RTC GB r1.0 09.07.2013.docx
1
3
2
RG-LX gascke
(optional)
4
Outputs
Compressor output acc. to par. "Con" and "COF"
Outputs unchanged
Outputs unchanged
Outputs unchanged
Outputs unchanged.
Outputs unchanged.
It depends on the "Ac2" parameter
It depends on the "bLL" parameter
Compressor and fans restarts
Output unchanged.
Temperature alarms "HA", "LA" "HA2" and "LA2" automatically stop as soon as the temperature
returns to normal values.
Alarms "EA" and "CA" (with i1F=bAL) recover as soon as the digital input is disabled.
Alarm "CA" (with i1F=PAL) recovers only by switching off and on the instrument.
14.3 OTHER MESSAGES
Pon
Keyboard unlocked.
PoF
Keyboard locked
noP
In programming mode: none parameter is present in Pr1
On the display or in dP2, dP3, dP4: the selected probe is nor enabled

15. TECHNICAL DATA

Housing: self extinguishing ABS.
Case: facia 38x185 mm; depth 76mm
Mounting : panel mounting in a 150x31 mm panel cut-out with two screws.
Distance between the holes 165mm
Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional)
Connections: Screw terminal block
Power supply: 230Vac or. 110Vac or 24Vac
Power absorption: 5VA max.
Display: 3 digits, red LED, 14,2 mm high.
Display: 3 digits, red LED, 14,2 mm high; Inputs: Up to 4 NTC or PTC probes.
Digital inputs: 2 free voltage
Relay outputs: Total current on loads MAX. 20A
compressor: relay SPST 20(8) A, 250Vac
light: relay SPST 8 or 16(3) A, 250Vac
Other output : buzzer (optional)
Serial output : TTL standard; Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM).
Internal clock back-up: 24 hours (only for model with RTC)
Kind of action: 1B; Pollution grade: 2;Software class: A.;
Rated impulsive voltage: 2500V; Over voltage Category: II
Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 2085% (no condensing)
Measuring and regulation range: NTC probe: -40÷110°C (-40÷230°F);
PTC probe: -50÷150°C (-58÷302°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable); Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
16. CONNECTIONS
Supply: 120Vac or 24Vac: connect to terminals 11-12
The X-REP output is optional
The light relay can be also 16(5)A according to the model

17. DEFAULT SETTING VALUES

Label
Name
Set Set point
Hy Differential
LS Minimum set point
US Maximum set point
Ot Thermostat probe calibration
P2P Second probe presence
OE Second probe calibration
P3P Third probe presence
O3 Third probe calibration
P4P Fourth probe presence
O4 Fourth probe calibration
OdS Outputs delay at start up
AC Anti-short cycle delay
Ac1 Second compressor start delay
rtr P1-P2 percentage for regulation
CCt Continuous cycle duration
CCS Set point for continuous cycle
COn Compressor ON time with faulty probe
COF Compressor OFF time with faulty probe
CH Kind of action
CF Temperature measurement unit
rES Resolution
Lod Probe displayed
rEd
2
X-REP display
dLy Display temperature delay
dtr P1-P2 percentage for display
ACH Kind of action for auxiliary relay
SAA Set Point for auxiliary relay
SHy Differential for auxiliary relay
ArP Probe selection for auxiliary relay
Sdd Auxiliary relay operating during defrost
ALP Alarm probe selection
ALc Temperat. alarms configuration
ALU MAXIMUM temperature alarm
ALL Minimum temperature alarm
AFH Differential for temperat. alarm recovery
XW10L
3 x 2mm.
2,5 mm
heat-resistant wiring and 6,3mm Faston
2
10%
Range
LS÷US
0,125.5°C/ 1 255°F
-50°CSET/-58°FSET
SET110°C/ SET  230°F
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
n=not present; Y=pres.
-1212°C /-120120°F
0÷255 min
0  50 min
0÷255s
0 ÷ 100 (100=P1 , 0=P2)
0.0÷24.0h
(-55.0÷150,0°C) (-67÷302°F)
0  255 min
0  255 min
cL÷Ht
°C  °F
in=integer; dE= dec.point
P1;P2
P1 – P2 – P3 – P4 – SEt – dtr
0 ÷ 20.0 min (10 sec.)
1 ÷ 99
CL; Ht
-50,0÷110°C / -58÷230°F
0,125.5°C/ 1 255°F
nP / P1 / P2 / P3/P4
n÷y
nP; P1; P2; P3; P4
rE= related to set;
Ab = absolute
Set110.0°C; Set÷230°F
-50.0°CSet/ -58°FSet
(0,1°C÷25,5°C) (1°F÷45°F)
Value
Level
3.0
- - -
2.0
Pr1
-50.0
Pr2
110
Pr2
0.0
Pr1
n
Pr1
0.0
Pr2
n
Pr2
0
Pr2
n
Pr2
0
Pr2
0
Pr2
1
Pr1
5
Pr2
100
Pr2
0.0
Pr2
3.0
Pr2
15
Pr2
30
Pr2
cL
Pr1
°C
Pr2
dE
Pr1
P1
Pr2
P1
Pr2
0.0
Pr2
50
Pr2
cL
Pr2
0,0
Pr2
2,0
Pr2
nP
Pr2
n
Pr2
P1
Pr2
Ab
Pr2
110,0
Pr1
-50,0
Pr1
2,0
Pr2
4/5