Alarm Delay (P004) - Siemens SITRANS WM300 MFA Operating Instructions Manual

Motion sensors
Hide thumbs Also See for SITRANS WM300 MFA:
Table of Contents

Advertisement

6.4.2

Alarm delay (P004)

For relay, alarm delay (P004) outputs Q2 and Q4 from probe B input.
Note
Once an alarm delay is programmed, no input is required to activate.
Enter a relay output delay in seconds (0-399). The delay avoids false alarms in conditions
which can go in and out of desired range setpoint frequently.
When value = > 0 then output relays are held maintained (Hi) for the set time period to allow
system to achieve process speed
Note
Typically used for a Slow Speed process, but will work with standard operating functions as
well.
Values
SITRANS WM300 MFA
Operating Instructions, 08/2018, A5E45090709-AA
Alarm Delay = ON
P004 ≥ 1 (1 = 1.00 Seconds)
Parameter assignment
6.4 Alarm delay
37