6.3.2

Start up delay (P002)

For relay outputs Q2 and Q4 from probe B input, input 2 must have an enable function
Note
Typically used for a slow speed process, but also compatible with standard operating
functions.
Enable to have a start up delay in seconds (0 to 399), delay allows process to get to
operational speed before a relay output will be generated.
When value = > 0 then output relays are maintained (Hi) for the set time period to allow
system to achieve process speed.
Values
SITRANS WM300 MFA
Operating Instructions, 08/2018, A5E45090709-AA
Startup Delay = ON
I2 = Hi (Active Hi transition from Lo – Hi)
Input I2 = 1 Enable (Momentary transition from Lo - Hi – Lo)
Input I2 = 0 Disabled
Parameter assignment
6.3 Start up delay
35