Parameter Descriptions
0-30 Custom Readout Unit
Option:
Function:
[171] lb/in²
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
0-31 Custom Readout Min Value
Range:
Function:
Size
[ -999999.99 -
This parameter allows selection of
related
100.00
the minimum. value of the custom-
*
CustomRea-
defined readout (occurs at zero
doutUnit]
speed). It is only possible to select a
value different to 0 when selecting a
linear unit in parameter 0-30 Custom
Readout Unit. For quadratic and cubic
units the minimum value is 0.
0-32 Custom Readout Max Value
Range:
100 Custom-
[ par. 0-31 -
ReadoutUnit
999999.99
*
CustomRea-
doutUnit]
0-37 Display Text 1
Range:
Function:
0
[0 -
In this parameter, it is possible to write an individual
*
25 ]
text string for display in the LCP or to be read via
serial communication. If to be displayed permanently,
select [37] Display Text 1 in
Parameter 0-20 Display Line 1.1 Small
0-21 Display Line 1.2 Small
0-22 Display Line 1.3 Small
0-23 Display Line 2 Large
0-24 Display Line 3 Large
Parameter 0-37 Display Text 1
is linked to 12-08 Host Name. Changing 12-08 Host
Name changes Parameter 0-37 Display Text 1 - but not
vice versa.
MG11CE02
Programming Guide
Function:
This parameter sets the max.
value to be shown when the
speed of the motor has reached
the set value for
parameter 4-13 Motor Speed High
Limit [RPM] or
parameter 4-14 Motor Speed High
Limit [Hz] (depends on setting in
parameter 0-02 Motor Speed
Unit).
Danfoss A/S © 03/2015 All rights reserved.
0-38 Display Text 2
Range:
Function:
0
[0 -
In this parameter, it is possible to write an individual
*
25 ]
text string for display in the LCP, or to be read via
serial communication. If to be displayed permanently,
select [38] Display Text 2 in:
Parameter 0-20 Display Line 1.1 Small
0-21 Display Line 1.2 Small
0-22 Display Line 1.3 Small
0-23 Display Line 2 Large
0-24 Display Line 3 Large
Press [
] or [
] to change a character. Press [
[
] to move the cursor. When a character is
highlighted by the cursor, this character can be
changed. A character can be inserted by placing the
cursor between 2 characters and pressing [
0-39 Display Text 3
Range:
Function:
0
[0 -
In this parameter it is possible to write an individual
*
25 ]
text string for display in the LCP or to be read via
serial communication. If to be displayed permanently
select Display Text 3 in parameter 0-20 Display Line
1.1 Small, 0-21 Display Line 1.2 Small, 0-22 Display
Line 1.3 Small, 0-23 Display Line 2 Large or
0-24 Display Line 3 Large. Press [
a character. Press [
When a character is highlighted by the cursor, this
character can be changed. A character can be
inserted by placing the cursor between 2 characters
and pressing [
] or [
3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled
Avoid accidental usage of the key.
[1]
Enabled
[Hand On] key enabled.
*
[2]
Password Avoid unauthorised start in Hand mode. If
parameter 0-40 [Hand on] Key on LCP is included
in My Personal Menu, define the password in
parameter 0-65 Personal Menu Password.
Otherwise, define the password in
parameter 0-60 Main Menu Password.
] and
] or [
].
] or [
] to change
] and [
] to move the cursor.
].
33