Danfoss VLT HVAC Drive FC 102 Programming Manual page 188

Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Parameter Descriptions
24-01 Fire Mode Configuration
Option:
3
3
[0]
Open
Loop
*
[3]
Closed
Loop
24-02 Fire Mode Unit
Option:
[0]
None
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[11]
RPM
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
186
Function:
NOTICE
Before adjusting the PID controller set
parameter 24-09 Fire Mode Alarm Handling,
[2] Trip, All Alarms/Test.
NOTICE
If [2] Enable-Run Reverse is selected in
parameter 24-00 Fire Mode Function, [3]
Closed Loop cannot be selected in
parameter 24-01 Fire Mode Configuration.
When fire mode is active, the motor runs with a
fixed speed based on a reference set. The unit is
the same as selected in parameter 0-02 Motor
Speed Unit.
When fire mode is active, the built-in PID
controller controls the speed based on the
setpoint and a feedback signal selected in
parameter 24-07 Fire Mode Feedback Source. Select
the unit in parameter 24-02 Fire Mode Unit. For
other PID controller settings use parameter group
20-** FC Closed Loop as for normal operation. If the
motor also is controlled by the built-in PID
controller when in normal operation, the same
transmitter can be used for both cases by
selecting the same source.
Function:
Select the desired unit when fire mode is active
and running in closed loop.
Danfoss A/S © 03/2015 All rights reserved.
®
VLT
HVAC Drive FC 102
24-02 Fire Mode Unit
Option:
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[75]
mm Hg
[80]
kW
[120] GPM
[121] gal/s
[122] gal/min
[123] gal/h
[124] CFM
[125] ft³/s
[126] ft³/min
[127] ft³/h
[130] lb/s
[131] lb/min
[132] lb/h
[140] ft/s
[141] ft/min
[145] ft
[160] °F
[170] psi
[171] lb/in²
[172] in WG
[173] ft WG
[174] in Hg
[180] HP
24-03 Fire Mode Min Reference
Range:
Size
related
*
Function:
Function:
[ -999999.999
Minimum value for the reference/
- par. 24-04
setpoint (limiting the sum of value in
FireModeUnit]
parameter 24-05 Fire Mode Preset
Reference and value of signal on
input selected in parameter 24-06 Fire
Mode Reference Source).
If running in open loop when fire
mode is active, the unit is selected by
the setting of parameter 0-02 Motor
Speed Unit. For closed loop, select the
unit in parameter 24-02 Fire Mode
Unit.
MG11CE02