Parameter Descriptions
NOTICE
The maximum current for the analog outputs 0-10 V is 1 mA.
NOTICE
Where live zero monitoring is used, it is important that any analog inputs not being used for the frequency converter,
that is, being used as part of the building management system decentral I/O, should have their live zero-function
disabled.
Terminal
Parameters
Analog inputs
X42/1
Parameter 26-00 Termi
nal X42/1 Mode, 26-1*
X42/3
Parameter 26-01 Termi
nal X42/3 Mode, 26-2*
X42/5
Parameter 26-02 Termi
nal X42/5 Mode, 26-3*
Analog outputs
X42/7
26-4*
X42/9
26-5*
X42/11
26-6*
Table 3.29 Relevant Parameters
It is also possible to read the analog inputs, write to the analog outputs, and control the relays, using communication via
the serial bus. In this instance, these are the relevant parameters.
Terminal
Parameters
Analog inputs (read)
X42/1
Parameter 18-30 Anal
og Input X42/1
X42/3
Parameter 18-31 Anal
og Input X42/3
X42/5
Parameter 18-32 Anal
og Input X42/5
Analog outputs (write)
X42/7
Parameter 18-33 Anal
og Out X42/7 [V]
X42/9
Parameter 18-34 Anal
og Out X42/9 [V]
X42/11
Parameter 18-35 Anal
og Out X42/11 [V]
Table 3.30 Relevant Parameters
Setting of on-board real time clock
The analog I/O option incorporates a real time clock with battery back-up. This can be used as back-up of the clock function
included in the frequency converter as standard. See chapter 3.2.8 0-7* Clock Settings.
The analog I/O option can be used for the control of devices such as actuators or valves, using the extended closed loop
facility, thus removing control from the building management system. See chapter 3.19 Parameters: 21-** Main Menu -
Extended Closed Loop. There are 3 independent closed-loop PID controllers.
MG11CE02
Programming Guide
Terminal
Parameters
Analog inputs
53
6-1*
54
6-2*
Analog output
42
6-5*
Terminal
Parameters
Analog inputs (read)
53
Parameter 16-62 Anal
og Input 53
54
Parameter 16-64 Anal
og Input 54
Analog output (write)
42
Parameter 6-53 Termin
al 42 Output Bus
Control
Danfoss A/S © 03/2015 All rights reserved.
Terminal
Parameters
Relays
Relay 1 Term 1, 2, 3
5-4*
Relay 2 Term 4, 5, 6
5-4*
Terminal
Parameters
Relays
Relay 1 Term 1, 2, 3
Parameter 16-71 Relay
Output [bin]
Relay 2 Term 4, 5, 6
Parameter 16-71 Relay
Output [bin]
NOTICE
Enable the relay outputs via control
word bit 11 (relay 1) and bit 12 (relay
2).
3
3
201

Advertisement

Table of Contents
loading

Table of Contents