Alarm Relay Channel Numbers; 8 And 16 Digital Input/Output Card - Honeywell X Series User Manual

Hide thumbs Also See for X Series:
Table of Contents

Advertisement

Alarm Relay Channel Numbers

The Alarm Relay cards are either 4 or 8 channels with a full length connector taking up 8
channels even though the cards only operate on 4 channels or 8 channels. The 8 channels
Alarm Relay card has 2 digital inputs available on the last 2 channels. There are no Digital
Inputs available on the 4 channels Alarm Relay card.

8 and 16 Digital Input/Output Card

The 16 channel Digital I/O card is not available on the eZtrend QXe recorders.
The
way connectors, the left connector for the first 8 channels and right connector for the second
8 channels. The pin-outs for 8 and 16 I/O cards are labelled from left to right, 1 to 16 on the
left side and 17 to 32 on the right. Each channel can be set up as an input or an output. For
output the relay is normally open type.
A Form A dry contacts relay is used for this type of card. The inputs are designed to accept
"Dry contact, no volt inputs".
26
Alarm Relay card 4 channel
Card
Channel
position
number
Slot G
1 to 4
Slot H
17 to 20
Slot I
33 to 36
Figure 2.10 Alarm Relay Card connector details
CH 1
CH 2
NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO
NC = Normally Closed
C = Common
NO = Normally Open
Digital Input/Output Card
Table 2.6 :
Digital
Card
Inputs
position
N/A
Slot G
N/A
Slot H
N/A
Slot I
CH 3
CH 4
CH 5
Relay contacts position
has 1A 24V DC rated relays that are connected via two 16-
Alarm Relay card 8 channel
Channel
number
1 to 8
17 to 24
33 to 40
CH 6
CH 7
CH 8
Channels 7 and 8 can
be set as Digital Inputs.
(Use C and NO)
43-TV-25-30 Iss.6 GLO Aug 07 UK
Digital
Inputs
7 & 8
23 & 24
39 & 40

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multitrend sxMinitrend qxEztrend qxe

Table of Contents