Honeywell X Series User Manual page 268

Hide thumbs Also See for X Series:
Table of Contents

Advertisement

Specification
Scales, Linear & Logarithmic
Input Isolation
Noise Rejection
(at 50/60Hz) +/-2%
Specification
Logging Method
Logging Types
Logging Rate
Fuzzy Logging
Specification
Enclosure/Bezel
Mounting Panel
Dimensions
Weight
Colour
Wiring Connections
262
Analogue Inputs
Normal and Scientific notation
Decimal Point automatic or programmable
Engineering units, user definable (10 characters)
Logarithmic: -38 min, to +38 max, (recommend up to 20 decades on one screen to ensure clarity)
300VAC channel-to-channel, channel-to-ground (Resistance thermometers are not isolated on
the QXe
Analogue Input card (std)
Common mode: 2Hz = -120dB, 5Hz = -120dB
Normal Mode: 2Hz = -80dB, 5Hz = -25dB
Analogue Input expansion card (option)
Common mode: 2Hz = -120dB, 5Hz = -120dB, 10Hz = -120dB
Normal Mode: 2Hz = -85dB, 5Hz = -80dB, 10Hz = -48dB
Sample, Average, Min/Max - can be set independently per pen
Continuous, Fuzzy
QX/SX 20 msec. to 60 hours per pen, QXe100 msec. to 60 hours per pen,
A secure data storage technique which delivers data compression ratio of 100:1 or more; self
teaching, storing the data at a variable rate to match the process
Zinc plated steel case with high impact resistant polycarbonate bezel; scratch resistant lens (Pol-
yethylene Terephthalate). NEMA 3 IP54 protection rating standard with NEMA 4X / IP66 (Front
face only) protection rating as an option.
Unlimited mounting angle. For the best view of the display the viewing angle should not exceed:
QX 55° from the left or right, 40° looking down and 50° looking up at the recorder display.
SX 70° from the left or right, 45° looking down and 55° looking up at the recorder display.
QXe 45° from the left or right, 10° looking down and 30° looking up at the recorder display.
Mounting adjustable for panel thickness of 2mm to 20mm. Adapter kits available for covering
existing panel cutouts.
QX/QXe Recorder - W: 144mm (5.67"), H: 144mm (5.67"), D: 200mm (7.87"). Additional 80mm
(3.15") clearance recommended for a straight type power cable and signal connectors. Cutout
138 x 138mm (5.43 x 5.43")
SX Recorder - W: 288mm (11.34"), H: 288mm (11.34), D: 200mm (7.87"). Additional 80mm
(3.15") clearance recommended for a straight type power cable and signal connectors. Cutout
281 x 281mm (11.06 x 11.06")
QX Recorder - 2.7 Kg (6lb) max.
SX Recorder - 10 Kg (22 lb) max.
QXe Recorder - 2.4 Kg (5.3lb) max.
Bezel: Black
IEC Power Plug. Removable terminal strip for input and alarm connections
Logging
Physical Parameters
43-TV-25-30 Iss.6 GLO Aug 07 UK

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multitrend sxMinitrend qxEztrend qxe