5.DISPLAY SETTINGS
5-5. Zero Tracking (ZT)
Zero tracking automatically compensates slow system drift, as well as small
zero-point shift due to residue objects on the sale such as debris, dirt and dust.
54
m+34
3
2
m+35
10
10
・ Zero tracking clear Final to zero at every specified period, if zero shift
during that period remains within the specified range.
・Allowed tracking period is from 0.0 to 9.9 seconds, and Zero
tracking range is from 0 to 9999 in 1/4 of scale division unit.
(0002=0.5 divisions, 0012=3 divisions)
Zero tracking is disabled if zero is specified for the period or
range.
Boundary of zero track
+
0
-
Tracking period
0
-1
Zero tracking period 0.0-9.9 sec
10
10
1
0
Zero tracking range 0-9999
10
10
From the point when it returned within the range,
counting will be resumed.
Weighing value
Tracking period
Tracking range