Technician Settings - Carrier ComfortVu TB-24-HM Installation And Operation Manual

Bacnet thermostat standard (24 vac model)
Hide thumbs Also See for ComfortVu TB-24-HM:
Table of Contents

Advertisement

Technician Settings (cont.)
P35 – Enable/Disable Freeze protection
"00" - Disable Freeze protection
"01" - Enable Freeze protection
Note: If enabled, freeze protection will start when the thermostat
is either ON or OFF and regardless of the current system
mode.
P36 – Freeze protection cut-in setpoint
Range:
8...15°C / 46...59°F
Default:
8°C / 46°F
The room ambient temperature which will trigger Heating ON.
P37 – Freeze protection cut-out setpoint
Range:
10...17°C / 50...63°F
Default:
10°C / 50°F
The room ambient temperature which will switch the Heating back OFF.
P40 – View filter counter (hours) – Read only
Range:
0...999 hours
The filter counter is related to Fan running time.
P41 – Reset filter time
Press the [+] button to reset the filter counter.
The display will change from "00" to "01" and back to "00".
P42 – Adjust filter alarm delay time counter (hours)
Range:
0...999 hours
Default: 0 hours (0 = Disable)
- 46 -
Disable freeze
Enable freeze
protection
protection
Freeze protection cut-in setpoint
(°C)
(°F)
Freeze protection cut-out setpoint
(°C)
(°F)
View filter
Counter (hours)
Reset filter
counter
Adjust filter alarm
delay time (hours)