Technician Settings (cont.)
P65 – Fan VFS proportional band in cooling
Range:
2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V fan speed from off closed to fully running.
P66 – Fan VFS proportional band in heating
Range:
2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V fan speed from off closed to fully running.
P67 – Fan VFS Low speed percent in cooling
Range:
0...30%
Default: 20%
P68 – Fan VFS Medium speed percent in cooling
Range:
30...60%
Default:
50%
P69 – Fan VFS High speed percent in cooling
Range:
60...100%
Default:
90%
P70 – Fan VFS Low speed percent in heating
Range:
0...30%
Default:
30%
- 53 -
VFS Proportional band in cooling
(°C)
(°F)
VFS Proportional band in heating
(°C)
(°F)
VFS Low %
in cooling
VFS Med %
in cooling
VFS High %
in cooling
VFS Low %
in heating

Hide quick links: